5.1.2 Redundancy toggle
冗余切换
If any of the following conditions occur at the Primary, a redundancy toggle is initiated deliberately between Primary and Secondary:
如果主(控制器)发生以下任何情况,在主(控制器)和从(控制器)之间主动发生冗余切换。
- the Prim/Sec TOGGLE switch of the controller is actuated,
- 启动控制器上的主/从开关
- the Prim/Sec button of the resource is actuated in commissioning mode,
- 调试模式下启动资源上的主/从按钮。
- the RESET switch is actuated > 5 s, resulting in a cold start of the Primary,
- 复位开关在>5秒后启动,导致主(控制器)冷启动。
- the system function “Force redundancy toggle” (PRIM_SEC) is executed.
- 执行系统功能“强制冗余切换”(PRIM_SEC)。
In typical applications, the Secondary will continue the application processing after 350 to 400 ms when a redundancy toggle is initiated deliberately. In the event of an error, the actual toggle time will generally be longer, as in addition to the time for change-over required by the controller, the error detection and the change of the connected field busses will take time.
在典型应用中,当有一启动冗余切换时,备(控制器)在350至400ms之后继续应用程序的处理。在错误发生时,实际的切换时间一般比较长,因为除了冗余切换所需时间之外,检查错误和连接现场总线变化也要消耗时间。